Results
--
Design Density
gpm/sq ft
--
Total Water Demand
gpm
--
Water Volume Required
gallons
Note: The area/density curves in NFPA 13 define the minimum design parameters. Select an operating point on or above the curve. Hose stream allowances per NFPA 13 Table 11.2.3.1.2: LH=100gpm, OH=250gpm, EH=500gpm.
Reference
NFPA 13 Figure 11.2.3.1.1 Area/Density Curves
LH: 0.10 gpm/ft2 over 1500 ft2
OH1: 0.15 to 0.10 gpm/ft2 over 1500-4000 ft2
OH2: 0.20 to 0.15 gpm/ft2 over 1500-4000 ft2
EH1: 0.30 to 0.20 gpm/ft2 over 2500-5000 ft2
EH2: 0.40 to 0.25 gpm/ft2 over 2500-5000 ft2
Total Demand = (Density x Area) + Hose Stream