Input Parameters

Results

--
Exhaust Rate
m3/s
--
Exhaust Rate
CFM
--
Plume Centerline Temp Rise
C
Note: Based on NFPA 92 Standard for Smoke Control Systems. Axisymmetric plume assumes fire is not against a wall. For wall or corner fires, use balcony spill plume or window plume equations instead.

Reference

NFPA 92 Axisymmetric Plume: m_dot = 0.071 * Qc^(1/3) * z^(5/3) + 0.0018 * Qc Qc = 0.7 * Q (convective fraction) deltaT = Qc / (m_dot * Cp) V_dot = m_dot / rho_smoke rho = 353 / T_smoke(K)