Results
--
Protection Design Area
ft²
--
Water Application Density
gpm/ft²
Note: NFPA 850 provides cable tray fire protection guidance for electric generating plants. IEEE 384 covers cable separation. Nuclear plants follow NRC Regulatory Guide 1.189. Use IEEE 1202 (vertical tray flame test) rated cables where possible. Linear heat detection or VESDA air sampling provides fastest response.
Reference
NFPA 850 / IEEE 384 Cable Tray Protection:
Design Area = Tray Width (ft) * (Tray Length + 40 ft)
Base Density: 0.30 gpm/ft² (PVC), 0.20 gpm/ft² (FR-rated)
Stack Adder: +0.05 gpm/ft² per additional tray
Fill Factor: 1.10 for fill > 50%
Total Flow = Design Area * Adjusted Density
Ref: NFPA 850 Sec 9.4, NRC RG 1.189