CO2 Suppression System Sizing

Calculate carbon dioxide fire suppression requirements per NFPA 12. CO2 systems are used for total flooding and local application in industrial settings.

Total area of openings that cannot be closed during discharge
Minimum expected enclosure temperature

NFPA 12 Design Concentrations

Hazard Type Min Concentration Discharge Time
Surface Fire (A/B)34%1 minute
Deep-Seated Fire50%7 minutes
Electrical Equipment50%1 minute
Rotating Equipment34%1 minute

Understanding CO2 Suppression Systems

Total Flooding

Total flooding systems fill the entire protected enclosure with CO2 to achieve the design concentration. The enclosure must be reasonably tight to maintain concentration during soak time.

Local Application

Local application systems discharge CO2 directly onto the hazard surface. Used for specific equipment or processes where total flooding is not practical.