Input Parameters

Results

--
Sprinkler Density Required
gpm/ft²
--
Total Sprinkler Flow
gpm
--
Fill/Packing Area
ft²
--
Exposure Risk Level
Note: FM Global DS 1-6 recommends internal sprinkler protection for all cooling towers with combustible fill within 50 ft of a building. Major losses have occurred from cooling tower fires spreading to adjacent structures. FRP and PVC fills burn rapidly. Provide linear heat detection and automatic sprinklers within the fill section.

Reference

FM Global DS 1-6 Cooling Tower Protection: Sprinkler Density: 0.25 gpm/ft² (FRP/PVC), 0.30 gpm/ft² (wood) Total Flow = Plan Area * Density Proximity Adder: +0.05 gpm/ft² if < 20 ft from building Non-combustible fill: detection only Plan Area = Length * Width Ref: FM Global DS 1-6, NFPA 214