Results
--
Sprinkler Density Required
gpm/ft²
--
Total Sprinkler Flow
gpm
Note: FM Global DS 1-6 recommends internal sprinkler protection for all cooling towers with combustible fill within 50 ft of a building. Major losses have occurred from cooling tower fires spreading to adjacent structures. FRP and PVC fills burn rapidly. Provide linear heat detection and automatic sprinklers within the fill section.
Reference
FM Global DS 1-6 Cooling Tower Protection:
Sprinkler Density: 0.25 gpm/ft² (FRP/PVC), 0.30 gpm/ft² (wood)
Total Flow = Plan Area * Density
Proximity Adder: +0.05 gpm/ft² if < 20 ft from building
Non-combustible fill: detection only
Plan Area = Length * Width
Ref: FM Global DS 1-6, NFPA 214