Input Parameters

Results

--
Required Airflow
CFM
--
Closed Door Leakage
CFM
--
Open Door Flow
CFM
--
Estimated Fan HP
HP
Note: IBC Section 3007 and NFPA 92 require elevator hoistway pressurization for fire service access elevators and occupant evacuation elevators. Minimum pressure differential is 0.05 in. w.g. with all doors closed.

Reference

NFPA 92 Elevator Pressurization: Closed Door Leak = 2610 x A_leak x sqrt(dP) per floor Open Door Flow = N_open x Door Area x 200 ft/min Fan HP = (CFM x SP) / (6356 x Efficiency) Stack Effect ~ 0.03 in.w.g. per floor