Emergency & Exit Lighting Calculator
Calculate emergency lighting and exit sign requirements per NFPA 101 Life Safety Code and IBC.
NFPA 101 Illumination Requirements
| Location | Min. Level | Duration |
|---|---|---|
| Means of Egress | 1.0 fc (avg) | 90 min |
| Initial (first 10 sec) | 1.0 fc (avg) | 10 sec |
| At End of 90 min | 0.6 fc (min) | - |
| Max:Min Ratio | 40:1 | - |
Emergency Lighting Requirements
Illumination Levels
NFPA 101 requires 1.0 fc average along the path of egress, with minimum 0.6 fc at any point. Maximum uniformity ratio is 40:1.
Duration
Emergency lighting must operate for at least 90 minutes upon loss of normal power. Battery backup or generator required.
Exit Signs
Exit signs must be visible from 100 ft maximum viewing distance. Letters minimum 6" high with 3/4" stroke. Self-luminous or externally illuminated.