Input Parameters

Results

--
Minimum Operating Pressure
psi
--
Design Sprinklers (12 or 15)
--
Sprinkler Flow Demand
gpm
--
Total Demand + Hose
gpm
Note: ESFR (Early Suppression Fast Response) sprinklers are designed to suppress (not just control) fires in rack storage. They require specific ceiling heights, deflector-to-storage clearances, and unobstructed ceilings. No in-rack sprinklers are needed when ESFR is properly applied. Obstructions below ESFR sprinklers can severely impact performance.

Reference

ESFR Design per NFPA 13: Q = K × sqrt(P) per sprinkler Design: 12 sprinklers (wet), 15 sprinklers (dry) K-factors: 14.0, 16.8, 22.4, 25.2 Hose stream: 250 gpm Min clearance: 36 inches (storage to deflector) Total Demand = (N × K × sqrt(P)) + Hose Stream