Fire Alarm Battery Calculator

Calculate secondary power battery capacity for fire alarm systems per NFPA 72 requirements.

From panel specifications - typically 100-300 mA
Typical smoke detector: 0.2-0.5 mA standby
Total load per NAC circuit during alarm

NFPA 72 Secondary Power Requirements

System Type Standby Alarm
Protected Premises24 hours5 min
Central Station24 hours5 min
Emergency Voice/Alarm24 hours15 min
Supervising Station60 hours5 min

Battery Calculation Notes

Safety Factor

Add 20% to calculated capacity to account for battery aging and temperature variations. Batteries lose capacity over time.

Standard Sizes

Common 12V SLA batteries: 7AH, 12AH, 18AH, 26AH, 33AH, 40AH, 55AH, 75AH, 100AH. Select next size up from calculated.

Recharge Time

NFPA 72 requires full recharge within 48 hours. Charger must be sized appropriately for battery capacity.