Fire Alarm Battery Calculator
Calculate secondary power battery capacity for fire alarm systems per NFPA 72 requirements.
NFPA 72 Secondary Power Requirements
| System Type | Standby | Alarm |
|---|---|---|
| Protected Premises | 24 hours | 5 min |
| Central Station | 24 hours | 5 min |
| Emergency Voice/Alarm | 24 hours | 15 min |
| Supervising Station | 60 hours | 5 min |
Battery Calculation Notes
Safety Factor
Add 20% to calculated capacity to account for battery aging and temperature variations. Batteries lose capacity over time.
Standard Sizes
Common 12V SLA batteries: 7AH, 12AH, 18AH, 26AH, 33AH, 40AH, 55AH, 75AH, 100AH. Select next size up from calculated.
Recharge Time
NFPA 72 requires full recharge within 48 hours. Charger must be sized appropriately for battery capacity.