Input Parameters

Results

--
Flow from Hydrant
gpm
--
Total Flow (all outlets)
gpm
--
Residual Pressure
psi
--
Available Flow at 20 psi
gpm
Note: Fire hydrant flow tests per NFPA 291 use pitot gauges to measure velocity pressure at flowing outlets. The discharge coefficient depends on outlet geometry. Results are plotted on N^1.85 graph paper to determine water supply capacity for fire protection design.

Reference