Input Parameters

Results

--
Required Dike Volume
gallons
--
Minimum Dike Floor Area
ft²
--
Minimum Dike Wall Height
ft
--
Potential Spill Fire Area
ft²
Note: NFPA 30 Section 22.11 requires containment of the largest single tank volume within a diked area. Dike walls shall not exceed 6 ft in height. Drainage must accommodate 10-year, 24-hour rainfall. Coordinate with NFPA 30 Table 22.4.2.1 for tank spacing within dikes.

Reference

NFPA 30 Sec 22.11 Dike/Containment: Dike Volume >= Largest Tank Volume + Tank Displacement Dike Area = Required Volume (ft³) / Usable Depth Usable Depth = Design Depth - Freeboard - Rainfall Wall Height = Usable Depth + Freeboard + Rain Allowance 1 ft³ = 7.48 gallons Spill Fire Area = Dike Floor Area (worst case)