Fire Hose Friction Loss

Calculate friction loss in fire hose using standard coefficients.

Positive = uphill, Negative = downhill

Wyes, siamese, etc. (5 PSI each)

Quick Reference - FL per 100 ft

Hose 100 GPM 150 GPM 200 GPM 250 GPM
1.75"15.5356297
2.5"24.5812.5
3" LDH0.681.52.74.2
5" LDH0.080.180.320.5

Formula: FL = C x (Q/100)^2 x (L/100)