Input Parameters

Results

--
Hydrants Needed for NFF
--
Total Available Capacity
gpm
--
Flow Surplus/Deficit
gpm
--
Max Spacing per ISO
ft
Note: ISO evaluates hydrant distribution as part of the Public Protection Classification (PPC). Hydrants must be within specified distances and provide adequate flow. IFC Appendix C provides additional guidance on hydrant spacing for new developments.

Reference

ISO Hydrant Distribution Credit: Distance Factor: 0-300 ft = 100%, 300-600 ft = 85%, 600-1000 ft = 70%, >1000 ft = 50% Total Capacity = N x Avg Capacity x Distance Factor Hydrants Needed = NFF / (Avg Capacity x Distance Factor) Max Spacing (ISO): <=1000 gpm=600 ft, <=2500=500 ft, <=3500=450 ft, >3500=400 ft IFC Appendix C: 300-600 ft spacing based on fire flow