Note: NFPA 72 Section 17.6 governs detector spacing. Intelligent/addressable detectors use same spacing rules as conventional. High ceilings, beams, joists, and HVAC diffusers all affect spacing. Smoke detectors limited to 30ft ceiling height per NFPA 72.
Reference
Smooth Ceiling: Spacing = Listed Spacing
Smoke Detectors: 30ft base, reduced for high ceilings per NFPA 72 Table 17.6.3.5.1
Heat Detectors: 50ft (standard) or 70ft (high-temp)
Beam Depth > 4": Spacing reduced per beam-to-ceiling ratio
Grid: N_length = ceil(L/S), N_width = ceil(W/S)
Total = N_length x N_width