Notification Appliance Calculator

Calculate horn/strobe placement, sound levels, and visual notification requirements per NFPA 72.

Wall mount: 80-96" AFF typical. Ceiling: actual ceiling height.

NFPA 72 Wall-Mount Strobe Spacing

Room Size (max) One Strobe (cd)
20 x 20 ft15 cd
28 x 28 ft30 cd
40 x 40 ft60 cd
50 x 50 ft75 cd
54 x 54 ft110 cd
55 x 55 ft135 cd
60 x 60 ft185 cd

Notification Requirements

Visual (Strobes)

Required in all public/common areas and restrooms. Candela based on room size. Synchronized flashing required.

Audible (Horns/Speakers)

15 dBA above ambient or 5 dBA above max sound (1 min). Sleeping areas: 75 dBA at pillow level.

ADA Compliance

Visual notification required where audible is used. Mount 80-96" AFF for wall units. Strobe intensity per Table 18.5.5.4.1.