Input Parameters

Results

--
Design Concentration
%
--
Agent Quantity Required
lb
--
Containers Required (100 lb)
--
Estimated Nozzles
Note: Novec 1230 has zero ozone depletion potential and a GWP of 1, making it the most environmentally friendly clean agent. 10% safety factor applied above minimum extinguishing concentration.

Reference

NFPA 2001 Clean Agent Fire Extinguishing Systems Novec 1230 (FK-5-1-12) Design Concentrations: Class A Surface: 4.2% Class B Heptane: 5.3% Class C Electronics: 5.3% Telecom/Data Center: 5.8% Weight: W = (V / s) × [Cd / (100 - Cd)] NOAEL: 10.0%, LOAEL: >10.0% GWP: 1 (vs FM-200 GWP: 3220)