Reference
NFPA 2001 Clean Agent Fire Extinguishing Systems
Novec 1230 (FK-5-1-12) Design Concentrations:
Class A Surface: 4.2%
Class B Heptane: 5.3%
Class C Electronics: 5.3%
Telecom/Data Center: 5.8%
Weight: W = (V / s) × [Cd / (100 - Cd)]
NOAEL: 10.0%, LOAEL: >10.0%
GWP: 1 (vs FM-200 GWP: 3220)