Note: Pipe schedule method is limited to 5,000 sq ft (LH) or 5,000 sq ft (OH) per floor. Systems exceeding these limits or in EH occupancies require hydraulic calculations per NFPA 13 Section 28.
Reference
NFPA 13 Pipe Schedule Method (Section 23.5)
Light Hazard - Table 23.5.3.1:
1" = 2 heads, 1.25" = 3 heads, 1.5" = 5 heads, 2" = 10 heads
Ordinary Hazard - Table 23.5.3.2:
1" = 2 heads, 1.25" = 3 heads, 1.5" = 5 heads, 2" = 8 heads
Max area: 52,500 sq ft for pipe schedule systems