Results
--
Mass Entrainment Rate
kg/s
--
Plume Temperature Rise
C
Note: The plume configuration significantly affects entrainment. A wall plume entrains less air than an axisymmetric plume for the same fire, reducing exhaust requirements. Corner plumes entrain even less. Always verify plume type based on fire location.
Reference
NFPA 92 Plume Equations:
Axisymmetric: m = 0.071*Qc^(1/3)*z^(5/3) + 0.0018*Qc
Wall: mirror image method (2x fire, half entrainment)
Corner: mirror image (4x fire, 1/4 entrainment)
Balcony Spill: m = 0.36*(Q*W)^(1/3)*(z+0.25*Hb)
Flame Height: zl = 0.166*Qc^(2/5)