Fire Pump Controller Sizing (NFPA 20 / NEC 695):
FLA = (HP × 746) / (V × 1.732 × PF × eff)
LRA ≈ 6-8 × FLA (across-the-line start)
CB sizing: 300% FLA per NFPA 20 / NEC 695.4(b)(2)
Conductor: 125% FLA per NEC 695.6
Controller must be listed for fire pump service per UL 218.