Fire Pump Curve Analysis
Analyze pump performance at various operating points per NFPA 20.
NFPA 20 Pump Curve Requirements
| Flow Point | Min Pressure | Max Pressure |
|---|---|---|
| 0% (Churn) | 101% | 140% |
| 100% (Rated) | 100% | 100% |
| 150% (Overload) | 65% | - |