Results
--
Min Operating Pressure
psi
--
Water Supply Duration
min
--
Min Tank Size (if tank)
gallons
Note: NFPA 13D applies to one- and two-family dwellings and manufactured homes. NFPA 13R applies to residential occupancies up to 4 stories. Both allow omission of sprinklers in closets, bathrooms under 55 sq ft, and some other small spaces. Listed residential sprinklers are required.
Reference
NFPA 13D: 2 sprinklers, 10 min duration, min 13 gpm/head
NFPA 13R: 2 sprinklers (dwelling), 15 min duration
P_min = (Q_min / K)^2, minimum 7 psi
Design Flow = Q_per_head × N
Tank Volume = Design Flow × Duration