Results
--
Stair Capacity
persons
--
Estimated Evacuation Time
min
--
Minimum Stairs Required
Note: Stairwell capacity per IBC Section 1005 and SFPE Handbook of Fire Protection Engineering. Evacuation time is approximate - actual times depend on occupant characteristics, pre-movement time, and stair congestion.
Reference
IBC 1005.1: Stair width factor = 0.3 in/person (non-sprinklered), 0.2 in/person (sprinklered)
Effective width = Clear width - 12 in (boundary layers per SFPE)
Flow rate Fs = 18.5 persons/min/ft effective width (SFPE Handbook)
Stair descent speed ~1.0 ft/s
Min 2 exits required per IBC 1021.1