Input Parameters

Results

--
Required Airflow
CFM
--
Flow Through Open Doors
CFM
--
Total Leakage Flow
CFM
--
Min Fan Static Pressure
in. w.g.
Note: NFPA 92 requires minimum 0.05 in. w.g. across closed doors and minimum 200 ft/min through open doors. Stack effect can significantly increase pressure requirements in tall buildings. Consider wind effects on exterior walls.

Reference

NFPA 92 Stairwell Pressurization: Door Flow = Num Open Doors x Door Area x 200 ft/min Leakage = 2610 x A_leak x sqrt(dP) per floor Total CFM = Door Flow + Leakage + Envelope Leakage Fan SP = dP + Duct Loss + Stack Effect