Input Parameters

Results

--
Minimum Pipe Diameter
in
--
Selected Pipe Size
in
--
Actual Velocity
ft/s
--
Suction Friction Loss
psi
Note: NFPA 20 Section 4.18 requires suction piping to be at least one nominal size larger than the pump suction flange. Suction velocity should not exceed 15 ft/s. Low friction loss in suction piping is critical to maintain adequate NPSHa.

Reference

Fire Pump Suction Pipe Sizing (NFPA 20): Min dia from velocity: d = sqrt(0.4085 × Q / Vmax) NFPA 20 Sec 4.18: suction pipe >= 1 size larger than pump connection Max velocity: 15 ft/s (NFPA 20), 10 ft/s preferred Friction: p = 4.52 × Q^1.85 / (C^1.85 × d^4.87) Keep suction losses minimal for adequate NPSHa.