Results
--
Tank-to-Tank Spacing
ft
--
Tank-to-Property Line
ft
--
Dike Wall-to-Tank Shell
ft
Note: NFPA 30 Table 22.4.2.1 provides prescriptive minimum distances for aboveground storage tanks. Protected tanks have approved foam or water spray systems. Class IA/IB liquids (gasoline, acetone) require greatest separation. Always verify against the current edition of NFPA 30 and local AHJ requirements.
Reference
NFPA 30 Table 22.4.2.1 Tank Spacing:
Class I Tank-to-Tank: D/4 to D/2 (protected vs unprotected)
Class I Tank-to-Property: max(1.5*D, H) unprotected; max(D, H) protected
Tank-to-Building: max(property distance, 25 ft)
Dike-to-Tank Shell: max(H/3, 5 ft)
Minimum tank-to-tank: 3 ft regardless